<?xml version="1.0" encoding="UTF-8"?><?xml-stylesheet type="text/xsl" href="static/style.xsl"?><OAI-PMH xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/ http://www.openarchives.org/OAI/2.0/OAI-PMH.xsd"><responseDate>2026-11-21T01:26:00Z</responseDate><request verb="GetRecord" identifier="oai:macsphere.mcmaster.ca:11375/33650" metadataPrefix="dim">https://prod-ms-be.lib.mcmaster.ca/server/oai/request</request><GetRecord><record><header><identifier>oai:macsphere.mcmaster.ca:11375/33650</identifier><datestamp>2026-10-03T07:06:51Z</datestamp><setSpec>com_11375_271</setSpec><setSpec>col_11375_272</setSpec></header><metadata><dim:dim xmlns:dim="http://www.dspace.org/xmlns/dspace/dim" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xmlns:doc="http://www.lyncode.com/xoai" xsi:schemaLocation="http://www.dspace.org/xmlns/dspace/dim http://www.dspace.org/schema/dim.xsd">
   <dim:field mdschema="dc" element="contributor" qualifier="advisor">Cotton, James</dim:field>
   <dim:field mdschema="dc" element="contributor" qualifier="author">Riascos Uribe, Leonor Sofia</dim:field>
   <dim:field mdschema="dc" element="contributor" qualifier="department">Mechanical Engineering</dim:field>
   <dim:field mdschema="dc" element="date" qualifier="accessioned">2026-10-02T20:21:19Z</dim:field>
   <dim:field mdschema="dc" element="date" qualifier="issued">2026</dim:field>
   <dim:field mdschema="dc" element="identifier" qualifier="uri">https://hdl.handle.net/11375/33650</dim:field>
   <dim:field mdschema="dc" element="identifier" qualifier="uri">https://doi.org/10.71548/25420</dim:field>
   <dim:field mdschema="dc" element="description" qualifier="abstract">Local Distribution Companies (LDCs) play a critical role in managing, operating, and planning electrical infrastructure within communities, particularly as energy consumption patterns shift. The accelerating growth of the population, the increasing frequency of extreme weather events, the initiatives to decrease the consumption of fossil fuels to achieve a net-zero economy by 2050, and the expansion of new technologies present significant challenges that necessitate a comprehensive understanding of how these factors interact and influence electrical infrastructure.
This thesis presents a methodology for forecasting electricity usage by integrating emerging technologies and demographic trends with historical electricity consumption patterns and weather data, using the City of Burlington as a case study. The research specifically examines the impact of electrified heating loads that arise from the adoption of various electrification technologies, including air-source heat pumps, ground-source heat pumps, and thermal networks. Additionally, it quantifies and models the effects of varying adoption rates of light-duty electric vehicles (EVs) on local electrical infrastructure, with a focus on vehicle efficiency and charging scenarios.
The methodology employs a representative weather profile and posits a constant population growth rate when modeling the loads. Utilizing a Long Short-Term Memory (LSTM) model, the study forecasts residential and commercial baseload demand, projecting a winter peak demand of 241 MW and a summer peak of 485 MW by 2050, rates that surpass the city's currently assigned capacity of 479 MW. The analysis further explores the implications of electrifying 60% of residential and 55% of commercial heating using air-source and ground-source heat pumps, predicting that winter peak demand could rise to 581 MW based on factors such as system efficiency, capacity, and sizing.
Moreover, the anticipated surge in EV adoption, projected to reach 100% of sales by 2050, is expected to significantly alter energy consumption patterns. Under an unmanaged charging scenario, peak consumption may experience noteworthy increases: by 2050, winter peak demand could escalate from 581 MW to 751 MW, while summer peak demand could rise from 485 MW to 604 MW.
If LDCs do not adequately prepare for the electrification trajectory through 2050, considerable infrastructure deficits are likely to emerge. These deficits may necessitate the addition of at least 21 new 27.6 kV feeders to accommodate the forecasted increase in electricity demand. Furthermore, the widespread adoption of electrified heating technologies and electric vehicles is projected to exceed the capacity of existing infrastructure as early as 2032. Full electrification of the heating load—achieved through air-source and ground-source heat pumps—is expected to elevate winter peak demand to 2.3 GWh, thereby requiring a minimum of 142 feeders of 27.6 kV to support the increased load.
Importantly, the study suggests that meeting 100% of the heating load by 2050 may be feasible through a strategic combination of 70% thermal networks and 30% ground-source heat pumps. This approach could generate a winter peak demand of 887 MW, effectively satisfying the heating requirements of both residential and commercial sectors by harnessing local waste heat within the community.</dim:field>
   <dim:field mdschema="dc" element="description" qualifier="degreetype">Thesis</dim:field>
   <dim:field mdschema="dc" element="description" qualifier="degree">Master of Applied Science (MASc)</dim:field>
   <dim:field mdschema="dc" element="language" qualifier="iso">en</dim:field>
   <dim:field mdschema="dc" element="title">Methodology Development to Quantify the Impact of Heating and Vehicle Electrification on Local Electric Infrastructure by 2050</dim:field>